3.2.1 (Optional) Refrigerant R410A

Do not use low-quality refrigerant. Huawei is not responsible for any damage
caused by low-quality refrigerant.
Follow these suggestions to choose high-quality refrigerant:
1.
2.
Figure 3-3 Checking refrigerant
Table 3-1 Mapping between temperatures and R410A saturation pressure
Tempe
rature
(°C)
0
1
2
3
Issue 06 (2020-08-19)
Optional: This material can be purchased from Huawei or prepared by
customers.
Engineering purchase: This material will not be delivered by Huawei, and
customers need to purchase it.
CA UTION
Contact the refrigerant producer to confirm the refrigerant authenticity.
Check the refrigerant by following the steps shown in
refrigerant indoors at a constant temperature and humidity for 24 hours. Use
a thermometer to measure the external surface temperature of the
refrigerant container, and connect a pressure gauge to the container to
measure its internal pressure. Determine the saturation pressure that
corresponds to the measured external surface temperature according to
3-1
and calculate the deviation from the measured internal pressure. If the
deviation is more than 0.2 MPa, the refrigerant is not qualified and should be
replaced.
Saturation
Pressure-
Surface
Pressure
(MPa)
0.7
0.73
0.75
0.78
Copyright © Huawei Technologies Co., Ltd.
Tempe
Saturation
rature
Pressure-
(°C)
Surface
Pressure (MPa)
19
1.31
20
1.35
21
1.39
22
1.43
3 Installation Guide
Figure
3-3: Keep the
Temper
Saturation
ature
Pressure-
(°C)
Surface
Pressure (MPa)
38
2.21
39
2.27
40
2.33
41
2.39
Table
28