NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
2.
Step 4 Add a SNMPv3 user.
1.
2.
Issue 06 (2020-08-19)
Figure 4-11 Setting read community
Tap the text box after Write Community, as shown in
Community as planned, tap
Figure 4-12 Setting write community
Tap Add under SNMP V3.
Enter a planned value for User Name, select values for Auth Protocol and
Prop Protocol from drop-down list boxes, and tap
4-13.
MD5 and DES protocols are not secure. It is recommended that you set Auth
Protocol to SHA, and set Prop Protocol to AES. The following operations use
the recommended settings as an example.
Figure 4-13 Setting the protocol type
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Figure
and then tap Submit.
, as shown in
4-12. Set Write
Figure
93