3.
4.
5.
Step 5 Tap the text box after SNMP Port, as shown in
actual port number, tap
Issue 06 (2020-08-19)
NO TICE
Passwords of an authentication protocol and proprietary protocol must
comply with the following policies:
– The password must consist of 8–15 characters and contain at least two
types of characters among uppercase letters (A–Z), lowercase letters (a–z),
and digits (0–9).
– A password must be different from the corresponding user name or
inverted user name.
– A password must not be a string containing duplicate sections, such as
12a12a12a.
Set SHA Password and Confirm Password as planned, and tap
shown in
Figure
4-14.
Figure 4-14 Setting an SHA password
Set AES Password and Confirm Password as planned, and tap
shown in
Figure
4-15.
Figure 4-15 Setting an AES password
Tap Submit.
Copyright © Huawei Technologies Co., Ltd.
Figure
, and then tap Submit.
4 Power-on and Commissioning
, as
, as
4-16. Set SNMP Port to the