Huawei NetCol8000-E220 User Manual page 153

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Alar
m ID
A018
-01
A018
-01
A018
-01
A018
-01
A018
-01
A018
-01
A025
-01
Issue 06 (2020-08-19)
Alarm
Alarm Name
Severit
y
WARNI
Indoor fan 5
NG
exceed
runtime
alarm
WARNI
Exhaust fan 1
NG
exceed
runtime
alarm
WARNI
Exhaust fan 2
NG
exceed
runtime
alarm
WARNI
Exhaust fan 3
NG
exceed
runtime
alarm
WARNI
Exhaust fan 4
NG
exceed
runtime
alarm
WARNI
Exhaust fan 5
NG
exceed
runtime
alarm
WARNI
Return air
NG
filter blocked
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Probable Cause
The accumulated
runtime of the fan
exceeds the alarm
threshold.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
The accumulated
runtime of the fan
exceeds the alarm
threshold.
1. Air filters are
blocked or dirty.
2. The differential
pressure switch is
faulty.
3. An inappropriate
threshold is set for
the differential
pressure switch.
4. The pressure tube
of the differential
pressure switch is
blocked or
disconnected.
5. The cables to the
differential pressure
switch are loose or
damaged.
Solution
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the fan, and clear the
accumulated runtime.
1. Maintain or replace
the air filters.
2. Replace the
differential pressure
switch.
3. Adjust the threshold
set for the differential
pressure switch.
4. Dredge or replace
the pressure tube.
5. Check the cables to
the differential
pressure switch.