Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Figure 3-5 Concrete platform (unit: mm)
(1) NetCol8000-E
Step 2 Determine the reference points for installing NetCol8000-Es on the concrete
platforms. Mark the reference points using a marker.
Step 3 Mark the mounting positions for the four corner fittings of a NetCol8000-E using
an ink fountain and long leather measuring tape.
When marking the mounting positions for corner fittings, ensure that the four
lines form a rectangle.
Step 4 Adjust the NetCol8000-E in the required direction, connect the steel hoisting ropes,
and hoist the NetCol8000-E onto the concrete platforms.
When hoisting a NetCol8000-E, ensure that the four corner fittings of the
NetCol8000-E are aligned with the marked mounting positions for corner fittings
on the concrete platforms.
Issue 06 (2020-08-19)
NO TICE
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) Concrete foundation
3 Installation Guide
34