NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Table 4-10 Proper system values (when the compressor is 3000 rpm)
Ambient
Temperat
ure
< 15°C
15–35°C
35–45°C
> 45°C
If the suction pressure, discharge pressure, and suction overheating degree is without normal
ranges, check and make sure that:
1. Charge refrigerant in an amount exactly as standard charge required. (Refrigerant charging
too much would result in high discharge pressure. Refrigerant charging too little would result
in low suction pressure, low discharge pressure, and high suction overheating degree.)
2. The air inlet and outlet of outdoor unit are without block. (The air inlet and outlet blockage
would result in high discharge pressure.)
Step 5 After charging refrigerant, close all valves.
Step 6 Tap
Step 7 Tap Shutdown on the home screen and confirm it.
----End

4.7 Wizard Startup

Prerequisites
Check that refrigerant is fully charged before performing the wizard startup.
Context
The startup wizard allows for commissioning of components such as the indoor
fan, spray system, exhaust fan, and cooling system. It also supports component
automatic operation and automatic device checking, and can output
commissioning report.
After you power on the smart cooling product for the first time, the screen
displays the Wizard Startup screen. If the smart cooling product is not started for
the first time, choose Maint > Wizard Startup to enter the Wizard Startup
screen.
Issue 06 (2020-08-19)
Proper Discharge
Pressure Range
1.5–2.5 MPa
1.5–3.1 MPa
2.5–3.8 MPa
3.1–4.15 MPa
NO TE
to exit the diagnostic mode.
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Proper Suction
Pressure Range
0.7–1.2 MPa
Proper
Overheating
Degree
8–15°C
111