Huawei NetCol8000-E220 User Manual page 107

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Table 4-8 Teamwork settings
Paramete
r
Teamwork
group No.
Smart
cooling
product
address
Enable
Teamwork
CAN
resistor
Teamwork
function
Issue 06 (2020-08-19)
Description
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
Smart cooling product
addresses should be
different from each
other.
Indicates the build-out
resistor status of each
smart cooling product in
a teamwork group. Set
the parameter if CAN
network is used.
Disable or enable the
teamwork function. If
the teamwork function is
disabled, this device is
operating according to
its own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Configuration
Principle
Set the assigned
teamwork control
number.
Set the assigned unit
address.
● Set this parameter
to No for non-
teamwork scenarios.
● For teamwork
scenarios, set this
parameter to Yes
for the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
Set this parameter
based on the onsite
device heat
distribution.
Default
Value
1
NA
No
Disable
98