B Netcol8000-E Repainting - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Prerequisites
Context
The NetCol8000-E exterior should be intact. If the NetCol8000-E surface is
bumped, scratched, or rusted, the paint should be repaired.
Issue 06 (2020-08-19)
B
Before repainting, communicate with the customer and inform the customer
that the front, rear,left, and right surfaces of the NetCol8000-E exterior are
level A surfaces, and bottom, and top surfaces are level B surfaces.
The color may be slightly different when level A surfaces are repainted.
Reach an agreement with the customer before repainting.
Acceptance criteria for repainting of level B surfaces: The repainted area
should have the same color as surrounding areas. The color difference ΔE
is not greater than 3. (Use a colorimeter to measure the color difference.
If a colorimeter is not available, check that no obvious edge exists
between the repainted area and its surrounding.) The paint should also
be free from bulges, scratches, flake-off, or cracks.
The outdoor area without shelters is not subject to bad weather conditions
such as raining, sandstorm, strong wind, or snowing during paint repair.
You have prepared the required paint that matches the color palette delivered
with equipment, the delivered color palette is the color of the product shell,
and the pantone number is RAL9003.
NO TE
Check the damage to the NetCol8000-E paint and prepare appropriate tools and materials.
The number of materials depends on site requirements.
Copyright © Huawei Technologies Co., Ltd.