Huawei NetCol8000-E220 User Manual page 240

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Context
Be careful when configuring alarms. Only professional maintenance personnel can
change alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
is displayed.
Figure 7-7 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Figure 7-8 Setting alarm parameter 2
----End
Issue 06 (2020-08-19)
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
To set an alarm threshold, follow the instructions in this section.
The method for setting each alarm is the same. This section describes how to
set Threshold of Supply air high temperature alarm to 45.
If you need to change alarm settings, log in as the Admin user.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
, as shown in
Figure
7-8.
7 FAQ
Figure 7-7
231

Advertisement

Table of Contents
loading

Table of Contents