Table 3-3 Recommended Cables
Item
Indoor unit
main power
cable
Indoor unit
standby
power cable
Indoor unit
cooling
power cable
Issue 06 (2020-08-19)
Maximum current
Recom
L1
mende
L2
d cross-
section
L3
al area
N
PE
Maximum current
Recom
L1
mende
L2
d cross-
section
L3
al area
N
PE
Maximum current
Recom
L1
mende
L2
d cross-
section
L3
al area
N
PE
Copyright © Huawei Technologies Co., Ltd.
NetCol8000-E220
141 A
2
4 x 70 mm
2
35 mm
71 A
2
4 x 70 mm
2
35 mm
70 A
2
4 x 70 mm
2
35 mm
3 Installation Guide
Remarks
The compressor
cooling system
obtains power from
the mains (factory
default).
Optional
If the compressor
obtains power from
the standby power,
the maximum
current of the
standby power is
141A.
Optional
(Optional) This
cable is required
only when the
compressor cooling
system is powered
independently.