Alarm
Alarm Name
Severit
y
MAJOR
Comp 1 high
discharge
pressure
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Probable Cause
1. The input power
of the outdoor unit
has an open phase,
incorrect phase
sequence, or is
unavailable.
2. Cables to the
indoor or outdoor
fan are not properly
connected.
3. The condenser
fins are dirty or
blocked.
4. The outdoor fan
or its drive is faulty.
5. The pressure
displayed is
different from the
actual pressure.
6. The refrigerant is
overfilled.
7. The exhaust fan
is faulty.
Solution
1. Check that the input
power is normal.
2. Check the cables to
the indoor and outdoor
fans.
3. Clean the condenser
fins.
4. Maintain or replace
the outdoor fan or its
drive.
5. Calibrate or replace
the pressure sensor.
6. Decrease certain
amount of refrigerant.
7. Maintain or replace
the exhaust fan.