Figure 4-4 Setting temperature and humidity values
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set the temperature and humidity values by referring to
Table 4-4 Parameter description
Parameter
Temperatur
e and
humidity
control type
Issue 06 (2020-08-19)
NO TE
You are not recommended to modify the parameters not listed in
Description
Cold aisle, Hot aisle, Return
air, or Supply air can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
Copyright © Huawei Technologies Co., Ltd.
4 Power-on and Commissioning
Table
4-4.
Table
4-4.
Configuration Principle
● When the application
scenario is cold or hot aisle
containment, you are
advised to choose Cold aisle
if the cold aisle T/H sensors
are configured, and choose
Supply air if the cold aisle
T/H sensors are not
configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose Return
air, and choose Cold aisle if
the cold aisle T/H sensors
are configured.
● Hot aisle is not
recommended.