Huawei NetCol8000-E220 User Manual page 104

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-16 Setting SNMP port
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
3.
4.
5.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and
successfully identified, tap Export File under MIB File to export the MIB file to the
USB flash drive for the customer's use in accessing a third-party EMS.
shows successful file export.
Issue 06 (2020-08-19)
NO TE
SNMP Port is set to 161 by default.
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
NO TE
Trap Port is set to null by default.
Select the SNMP Version. If a SNMPv3 user is configured, it is recommended
that SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, select a SNMPv3 user name, and then
tap
as shown in
Figure 4-17 Setting SNMP trap parameters
Tap Submit under SNMP Trap.
Copyright © Huawei Technologies Co., Ltd.
Figure
4-17.
4 Power-on and Commissioning
Figure 4-18
95

Advertisement

Table of Contents
loading

Table of Contents