Huawei NetCol8000-E220 User Manual page 267

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Menu
Issue 06 (2020-08-19)
Name
Supply air temp
to forcibly start
cooling
Return air temp
to forcibly start
cooling
Cold air temp to
forcibly start
cooling
Copyright © Huawei Technologies Co., Ltd.
Description
Specifies the temperature
threshold for forcibly
starting the cooling
composition when the
supply air temperature is
higher than the threshold.
Specifies the temperature
threshold for forcibly
starting the cooling
composition when the
return air temperature is
higher than the threshold.
Specifies the temperature
threshold for forcibly
starting the cooling
composition when the cold
air temperature is higher
than the threshold.
C Parameter Description
Default Value
25.0 ºC
43.0 ºC
27.0 ºC
258