NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Alar
m ID
A28E
-01
A28E
-01
A28E
-02
A28E
-02
A28E
-04
A28E
-04
A28E
-20
Issue 06 (2020-08-19)
Alarm
Alarm Name
Severit
y
CRITICA
Compressor 1
L
drive alarm
CRITICA
Compressor 2
L
drive alarm
CRITICA
Compressor 1
L
drive alarm
CRITICA
Compressor 2
L
drive alarm
CRITICA
Compressor 1
L
drive alarm
CRITICA
Compressor 2
L
drive alarm
CRITICA
Compressor 1
L
drive alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Probable Cause
1. The compressor
drive is faulty.
2. The compressor is
faulty.
1. The compressor
drive is faulty.
2. The compressor is
faulty.
1. The compressor
drive is faulty.
2. The compressor is
faulty.
1. The compressor
drive is faulty.
2. The compressor is
faulty.
The fans in the
compressor drive
are faulty.
The fans in the
compressor drive
are faulty.
1. The fans in the
compressor drive
are faulty.
2. The air vents of
the fans in the
compressor drive
are dirty or blocked.
3. The compressor
drive heat sink is
dirty, so the heat
exchange effect is
poor.
4. The electric
control box cavity is
dirty or blocked,
and the module
heat exchange
effect is poor.
5. The drive module
is faulty.
Solution
1. Maintain or replace
the compressor drive.
2. Maintain or replace
the compressor.
1. Maintain or replace
the compressor drive.
2. Maintain or replace
the compressor.
1. Maintain or replace
the compressor drive.
2. Maintain or replace
the compressor.
1. Maintain or replace
the compressor drive.
2. Maintain or replace
the compressor.
1. Check the fans in
the compressor drive.
1. Check the fans in
the compressor drive.
1. Check the fans in
the compressor drive.
2. Clean the air vents
of the fans in the
compressor drive.
3. Clean the heat sink
after power-off.
4. Clean the cavity
after power-off.
5. Replace the drive
module.
196