3.1 Installation Precautions

Storage
Before installing the NetCol8000, place it in dry, rainproof, fireproof, and
anticorrosive environments.
Installation Clearances
Reserve the following clearances around the device to facilitate operations and
ventilation.
Issue 06 (2020-08-19)
Place the NetCol8000 outdoors, and ensure that the NetCol8000 is protected
from dirt, rain, snow, other substances, or animals, and that the protective
film on the surface of the NetCol8000 is intact.
Do not expose the NetCol8000 to strong sunlight in summer. Otherwise, the
thermal insulation panels may be deformed.
If the NetCol8000 is packed with the entire system, do not stack them.
Check the NetCol8000 periodically.
Reserve at least 500 mm from the return air side to the wall.
Reserve at least 1500 mm from the maintenance doors side to the wall or
other device.
Reserve at least 1200 mm from the electric control box side to the wall or
other device.