Huawei NetCol8000-E220 User Manual page 59

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Figure 3-25 DN40 spray drainpipe dimensions (unit: mm)
(1) PPR external thread connector G (1–
1/2 inch)
Installing Water Pipes
● Clean the external water pipes before connecting them to the water inlet and
outlet pipes of the coil pipes of the NetCol8000.
● Connect the water inlet and outlet pipes of the NetCol8000 using thread
connectors. When connecting the water pipe, do not exert excessive force to
prevent damage to the coil pipe. (When connecting the pipes provided with the
NetCol8000, use two pipe wrenches or chain pliers.)
Take out the condensate water traps from attachment, and install them to 1, 2,
and 3 in
Use DN20 PPR pipes or stainless steel pipes and connectors G with 3/4 inch
external threads onsite to prepare water inlet pipes. If galvanized steel pipes are
used, stainless steel connectors must be used to ensure sealing.
Issue 06 (2020-08-19)
NO TICE
Figure
3-26.
Copyright © Huawei Technologies Co., Ltd.
(2) PPR equal-diameter
elbow
3 Installation Guide
(3) PPR pipe (Φ50 mm)
50