Warning messages generated by the control panel

WARNING
CAUSE
DOWNLOADING
Download function of panel has failed. No data
FAILED
has been copied from panel to drive.
DRIVE IS
Downloading is not possible while motor is
RUNNING
running.
DOWNLOADING
NOT POSSIBLE
NO
Cabling problem or hardware malfunction on
COMMUNICATION
Panel Link
(X)
(4) = Panel type not compatible with drive
application program version
NO FREE ID
Panel Link already includes 31 stations.
NUMBERS ID
NUMBER
SETTING NOT
POSSIBLE
NOT UPLOADED
No upload function has been performed.
DOWNLOADING
NOT POSSIBLE
UPLOADING
Upload function of panel has failed. No data
FAILED
has been copied from drive to panel.
WRITE ACCESS
Certain parameters do not allow changes while
DENIED
motor is running. If tried, no change is
PARAMETER
accepted, and warning is displayed.
SETTING NOT
Parameter lock is on.
POSSIBLE
WHAT TO DO
Make sure panel is in local mode.
Retry (there might be interference on link).
Contact ABB representative.
Stop motor. Perform downloading.
Check Panel Link connections.
Press RESET key. Panel reset may take up to
half a minute, please wait.
Check panel type and drive application
program version. Panel type is printed on
panel cover. Application program version is
stored in parameter 33.02.
Disconnect another station from link to free ID
number.
Perform upload function before downloading.
See chapter
Control
panel.
Retry (there might be interference on link).
Contact ABB representative.
Stop motor, then change parameter value.
Open parameter lock (see parameter 16.02).
287
Fault tracing