This section describes the different control schemes which can be used to control
the drive and the parameters to be set accordingly.

Control using digital inputs and Potentiometer Reference

Name
Description
Start/Stop Control
Selecting the source for start and stop signals of the
two external control locations, EXT1 and EXT2
for EXT1
Selecting between EXT1 and EXT2
Defining Start/Stop selection
Defining the direction control
Selecting the DI for Slowdown
Selecting signal Fast Stop
Selecting the signal High-end limit
Selecting the signal Low-end limit
Referencing EXT1
Selecting the source for the speed reference
(If AI1 is used: Setting analogue input AI1 limits, scale,
inversion)
Setting the reference limits
Setting the speed (frequency) limits
Setting the Slowdown reference
Setting acceleration/deceleration
Setting acceleration and deceleration times
Referencing EXT2
Selecting the source for the speed/torque reference
(If AI1 is used: Setting analogue input AI1 limits, scale,
inversion)
Setting the reference limits
Setting the speed (frequency) limits
Setting acceleration/deceleration
Setting acceleration and deceleration times
Application macros, control location EXT1/EXT2
Set parameters
Parameter value
11.02
EXT 1
10.01
DI1 F, DI2 R
10.03
REQUEST
10.09
DI4
10.10
10.12
10.13
11.03
AI1
(13.01, 13.02, 13.03,
13.04, 13.05, 30.01)
11.04,11.05
20.02, 20.01, (20.08,
20.07)
11.12
22.01
ACC/DEC DIR
22.02, 22.03, 22.10
11.06
AI1
(13.01, 13.02, 13.03,
13.04, 13.05, 30.01)
11.07,11.08
20.02, 20.01, (20.08,
20.07)
22.01
ACC/DEC DIR
22.02, 22.03, 22.10