Default Control Connections - ABB ACS800 Firmware Manual

Crane control program
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Default control connections

The figure below shows the external control connections for the Crane macro. The
markings of the standard I/O terminals on the RMIO board are shown.
1)
Parameter
10.03
should be
REQUEST.
2)
The US default settings differ as
follows:
DI1 DI2 Operation
0
0
Stop
1
0
Start Forward
0
1
Start Reverse
1
1
Stop
3)
See the wiring diagram on page
338
if used as power ackn signal.
4)
+24 V DC external auxiliary
voltage to the RMIO board.
For more information, see
24 V supply of RMIO board
117.
rpm
A
External
on page
X20
1
VREF
Reference voltage -10 V DC
2
GND
1 kohm < R
X21
1
VREF
Reference voltage 10 V DC
1 kohm < R
2
GND
3
AI1+
Speed reference 0(2) ... 10 V, R
4
AI1-
5
AI2+
By default, not in use. 0(4) ... 20 mA, R
100 ohm
6
AI2-
7
AI3+
By default, not in use. 0(4) ... 20 mA, R
100 ohm
8
AI3-
9
AO1+
Motor speed 0(4) ... 20 mA
speed, R
10
AO1-
L
11
AO2+
Output current 0(4) ... 20 mA
nom. current, R
12
AO2-
X22
1
DI1
Forward Start
2
DI2
Reverse Start
3
DI3
4
DI4
5
DI5
6
DI6
7
+24 V
+24 V DC, max. 100 mA
8
+24 V
9
DGND1 Digital ground
10
DGND2 Digital ground
11
DI IL
Start interlock (0 = stop)
X23
1
+24 V
Auxiliary voltage input/output, non-isolated,
24 V DC, 250 mA
2
GND
X25
1
RO11
Relay output 1
2
RO12
Open Brake
3
RO13
X26
1
RO21
Relay output 2
2
RO22
Running
3
RO23
X27
1
R031
Relay output 3
2
R032
Inverted fault
3
R033
Application macros, control location EXT1/EXT2
< 10 kohm
L
< 10 kohm
L
> 200 kohm
in
0 ... motor nom.
=
< 700 ohm
0 ... motor
=
< 700 ohm
L
2)
1, 2)
3)
4)
131
=