How to perform the limited start-up (covers only the basic settings)

Before you start, ensure that you have the motor nameplate data at hand.
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for safety instructions.
Check the installation. See the installation checklist in the appropriate hardware/installation
manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if:
- there is a risk of damage in case of incorrect direction of rotation, or
- a Standard ID run needs to be performed during the drive start-up. (ID run is essential only
in applications which require the ultimate in motor control accuracy.)
Apply mains power. The control panel first shows the panel
identification data ...
... then the Identification Display of the drive ...
... then the Actual Signal Display ...
The drive is now ready for the limited start-up.
ENTERING START-UP DATA MANUALLY (parameter group 99)
Select the language. The general parameter setting procedure is
described below.
The general parameter setting procedure:
- Press PAR to select the Parameter Mode of the panel.
- Press the double-arrow keys (
- Press the arrow keys (
- Press ENTER to activate the setting of a new value.
- Use the arrow keys (
double-arrow keys (
- Press ENTER to accept the new value (brackets disappear).
Select the Application Macro. The general parameter setting
procedure is given above.
The default value is CRANE.
Start-up and control through the I/O interface
SAFETY
POWER-UP
or
) to scroll the parameter groups.
or
) to scroll parameters within a group.
or
) to change the value. For fast change use the
or
).
CDP312 PANEL Vx.xx
.......
ACS800
ID NUMBER 1
1
->
0.0 rpm
O
FREQ
0.00 Hz
CURRENT
0.00 A
POWER
0.00 %
1
->
0.0 rpm
O
1
->
0.0 rpm
O
FREQ
0.00 Hz
CURRENT
0.00 A
POWER
0.00 %
1
->
0.0 rpm
O
99 START-UP DATA
01 LANGUAGE
ENGLISH
1
->
0.0 rpm
O
99 START-UP DATA
01 LANGUAGE
[ENGLISH]
1
->
0.0 rpm
O
99 START-UP DATA
02 APPLICATION MACRO
[ ]