Name/Selection
16.02
PARAMETER LOCK
OPEN
LOCKED
16.03
PASS CODE
0 ... 30000
16.04
FAULT RESET SEL
NOT SEL
COMM.CW
ON STOP
DI8
DI10
DI12
PARAM 16.11
16.05
USER MACRO IO
CHG
NOT SEL
DI8
DI9
DI10
COMM.CW
PARAM 16.13
16.06
LOCAL LOCK
OFF
ON
Description
Selects the state of the parameter lock. The lock prevents parameter changing.
The lock is open. Parameter values can be changed.
Locked. Parameter values cannot be changed from the control panel. The lock
can be opened by entering the valid code to parameter 16.03.
Selects the pass code for the parameter lock (see parameter 16.02).
Setting 358 opens the lock. Setting 584 opens the group 99 read only lock. The
value reverts back to 0 automatically.
Selects the source for the fault reset signal. The signal resets the drive after a
fault trip if the cause of the fault no longer exists.
Fault reset only from the control panel keypad (RESET key).
Reset through the fieldbus Control Word (bit 7), or with the RESET key of the
control panel.
Note: Reset through fieldbus Control Word (bit 7) is enabled automatically and
it is independent of parameter
to COMM.CW.
Reset along with the stop signal received through a digital input, or with the
RESET key of the control panel.
Digital input DI8 is the signal source.
Digital input DI10 is the signal source.
Digital input DI12 is the signal source.
Source selected with parameter 16.11.
Enables the change of the user macro through a digital input. See parameter
99.02. The change is only allowed when the drive is stopped. During the
change, the drive does not start.
Note: Always save the user macro with parameter
parameter settings, or reperforming the motor identification. The last settings
you have saved are loaded into use whenever the power is switched off and on
again or the macro is changed. Any unsaved changes will be lost.
Note: The value of this parameter is not included in the user macro. A setting
once made remains despite the user macro change.
Note: Selection of User Macro 2 can be supervised via relay output RO3. See
parameter
14.03
RO PTR3 for more information.
User macro change is not possible.
Digital input DI8 is the signal source.
Digital input DI9 is the signal source.
Digital input DI10 is the signal source.
Macro change through the fieldbus Control Word (bit 12).
Source selected with parameter 16.13.
Disables entering local control mode (LOC/REM key of the panel).
WARNING! Before activating, ensure that the control panel is not
needed for stopping the drive!
Local control allowed.
Local control disabled.
16.04
setting if parameter
99.02
FbEq
0
1
0 ... 30000
1
2
10.01
or
10.02
is set
3
4
5
6
7
after changing any
1
2
3
4
5
6
0
65535
Actual signals and parameters
173