CHAPTER 5: SETTINGS
configured to control the output contact. While the selected operand is Off, the output behaves as it does when in
service.
On restart, the
TEST MODE FORCING
to their default states.
NOTE

5.11.5 Phasor Measurement Unit test values

SETTINGS  TESTING  PMU TEST VALUES  PMU 1(6) TEST VALUES
 PMU 1
 TEST VALUES
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
setting and the force contact input and force contact output settings revert
PMU 1 TEST
FUNCTION: Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
PMU 1 VA TEST
ANGLE: 0.00°
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
PMU 1 VB TEST
ANGLE: –120.00°
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
PMU 1 VC TEST
ANGLE: 120.00°
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
PMU 1 VX TEST
ANGLE: 0.00°
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
PMU 1 IA TEST
ANGLE: –10.00°
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
PMU 1 IB TEST
ANGLE: –130.00°
PMU 1 IC TEST
MAGNITUDE: 1.000 kA
PMU 1 IC TEST
ANGLE: 110.00°
PMU 1 IG TEST
MAGNITUDE: 0.000 kA
PMU 1 IG TEST
ANGLE: 0.00°
PMU 1 TEST
FREQUENCY: 60.000 Hz
PMU 1 TEST
df/dt: 0.000 Hz/s
Range: Enabled, Disabled
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 20.000 to 60.000 Hz in steps of 0.001
Range: –10.000 to 10.000 Hz/s in steps of 0.001
TESTING
5
5-249