GE N60 Instruction Manual page 312

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CONTROL ELEMENTS
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
Application example
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group is to be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity
of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the
SETTING GROUPS FUNCTION
SETTING GROUPS BLK
GROUP 2 ACTIVATE ON
GROUP 3 ACTIVATE ON
5-196
Figure 5-96: Acknowledge mode
pre-existing
changed to 4 with
changed to 1 with
position 2
a pushbutton
: "Enabled"
: "Off"
: "SELECTOR 1 POS 2"
: "SELECTOR 1 POS 3"
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
changed to 2 with
a 3-bit input
a pushbutton
SETTINGS  CONTROL ELEMENTS  SETTING GROUPS
CHAPTER 5: SETTINGS
842736A1.CDR
menu:

Advertisement

Table of Contents
loading

Table of Contents