GE N60 Instruction Manual page 32

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

SPECIFICATIONS
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s:
Carry continuous:
Break (DC inductive, L/R = 40 ms):
Voltage
Current
24 V
1 A
48 V
0.5 A
2
125 V
0.3 A
250 V
0.2 A
Operate time:
Contact material:
FAST FORM-C RELAY
Make and carry:
Minimum load impedance:
Input voltage Impedance
2 W Resistor
250 V DC
20 K
120 V DC
5 K
48 V DC
2 K
24 V DC
2 K
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load
impedance.
Operate time:
Internal Limiting Resistor:
SOLID-STATE OUTPUT RELAY
Operate and release time:
Maximum voltage:
Maximum continuous current:
Make and carry:
for 0.2 s:
for 0.03 s:
Breaking capacity:
Operations/
interval
Break capability
(0 to 250 V DC)
CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT)
Capacity:
Isolation:
2-22
30 A as per ANSI C37.90
8 A
< 8 ms
silver alloy
0.1 A max. (resistive load)
1 W Resistor
50 K
2 K
2 K
2 K
< 0.6 ms
100  2 W
<100 s
265 V DC
5 A at 45°C; 4 A at 65°C
30 A as per ANSI C37.90
300 A
UL 508
Utility application
(autoreclose scheme)
5000 ops /
5 ops /
1 s-On, 9 s-Off
0.2 s-On, 0.2 s-Off
within 1 minute
1000 ops /
0.5 s-On, 0.5 s-Off
3.2 A
10 A
L/R = 10 ms
L/R = 40 ms
1.6 A
L/R = 20 ms
0.8 A
L/R = 40 ms
100 mA DC at 48 V DC
±300 Vpk
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Industrial application
10000 ops /0.2 s-On,
30 s-Off
10 A
L/R = 40 ms
CHAPTER 2: PRODUCT DESCRIPTION

Advertisement

Table of Contents
loading

Table of Contents