GE N60 Instruction Manual page 202

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP
The
NUMBER OF RECORDS
other factors, such as sample rate and the number of operational modules. There is a fixed amount of data storage for
oscillography; the more data captured, the less the number of cycles captured per record. See the
RECORDS  OSCILLOGRAPHY
configurations with corresponding cycles/record. The minimum number of oscillographic records is three.
Table 5-11: Oscillography cycles/record example
Records
CT/VTs
3
1
3
1
8
1
8
1
8
2
8
2
8
2
8
2
32
2
— A new record automatically overwrites an older record when
TRIGGER MODE
Overwrite."
TRIGGER POSITION
position of 25% consists of 25% pre- and 75% post-trigger data.
5
— Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
TRIGGER SOURCE
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records are cleared.
NOTE
5.3.8.2 Digital channels
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  DIGITAL CHANNELS
 DIGITAL CHANNELS
DIGITAL 1(63) CHANNEL
each oscillography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored.
5.3.8.3 Analog channels
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  ANALOG CHANNELS
 ANALOG CHANNELS
5-86
is selectable, but the number of cycles captured in a single record varies considerably based on
menu to view the number of cycles captured per record. The following table provides sample
Sample rate
Digital
8
0
16
16
16
16
16
16
16
16
16
63
32
63
64
63
64
63
— Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
— Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
DIGITAL CHANNEL 1:
Off
DIGITAL CHANNEL 63:
Off
— This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
ANALOG CHANNEL 1:
Off
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Analogs
Cycles/
record
0
14663
0
6945
0
3472
4
2868
4
1691
16
1221
16
749
16
422
16
124
TRIGGER MODE
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, any FlexAnalog parameter
See Appendix A for list
CHAPTER 5: SETTINGS
ACTUAL VALUES 
is set to "Automatic

Advertisement