Control Pushbuttons - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode,
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7
for information on major and minor self-test alarms.

5.3.13 Control pushbuttons

SETTINGS  PRODUCT SETUP  CONTROL PUSHBUTTONS  CONTROL PUSHBUTTON 1(7)
 CONTROL
 PUSHBUTTON 1
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained—if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-
programmable control pushbuttons.
The location of the control pushbuttons are shown in the following figures.
5
An additional four control pushbuttons are included on the standard faceplate when the N60 is ordered with the 12 user-
programmable pushbutton option.
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
5-94
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Figure 5-33: Control pushbuttons (enhanced faceplate)
Figure 5-34: Control pushbuttons (standard faceplate)
STATUS
EVENT CAUSE
IN SERVICE
VOLTAGE
TROUBLE
CURRENT
RESET
TEST MODE
FREQUENCY
TRIP
OTHER
USER 1
ALARM
PHASE A
PICKUP
PHASE B
USER 2
PHASE C
NEUTRAL/GROUND
USER 3
USER 4
USER 5
USER 6
USER 7
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Range: Disabled, Enabled
Range: Disabled, Enabled
Control pushbuttons
842813A1.CDR
THREE
STANDARD
CONTROL
PUSHBUTTONS
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
842733A2.CDR
CHAPTER 5: SETTINGS