GROUPED ELEMENTS
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
5.7.3 Power swing detect
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT
POWER SWING
DETECT
5
5-170
VOLTAGE ELEMENTS
SUPERVISING
ELEMENTS
POWER
POWER SWING
FUNCTION: Disabled
POWER SWING
SOURCE: SRC 1
POWER SWING
SHAPE: Mho Shape
POWER SWING
MODE: Two Step
POWER SWING
SUPV: 0.600 pu
POWER SW I2 SUPV ENAB:
Off
POWER SWING
I2 SUPV: 0.2 pu
POWER SWING FWD
REACH: 50.00
POWER SWING QUAD FWD
REACH MID: 60.00
POWER SWING QUAD FWD
REACH OUT: 70.00
POWER SWING FWD
RCA: 75°
POWER SWING REV
REACH: 50.00
POWER SWING QUAD REV
REACH MID: 60.00
POWER SWING QUAD REV
REACH OUT: 70.00
POWER SWING REV
RCA: 75°
POWER SWING OUTER
LIMIT ANGLE: 120°
POWER SWING MIDDLE
LIMIT ANGLE: 90°
POWER SWING INNER
LIMIT ANGLE: 60°
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
See page 5-180
See page 5-183
See page 5-185
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Mho Shape, Quad Shape
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
Range: 0.050 to 30.000 pu in steps of 0.001
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 0.10 to 500.00 ohms in steps of 0.01
Range: 40 to 90° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1
Range: 40 to 140° in steps of 1