PRODUCT SETUP
5.3.4.2 Serial ports
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  SERIAL PORTS
 SERIAL PORTS
5
,
RS232 BAUD RATE
RS485 COM2 BAUD RATE
ports. The faceplate RS232 port is intended for local use and has two options for baud rate. The rear COM2 port is RS485
and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software. This software can download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.
5.3.4.3 Ethernet network topology
The N60 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP
address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND
operation performed between their respective IP address and mask produces a different result. Communication becomes
unpredictable when more than one port is configured to the same subnet.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
5-28
 MODBUS PROTOCOL
PROTOCOL:
DNP 3.0
 DNP PROTOCOL
 DNP / IEC104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 IEC103
 PROTOCOL
RS232 BAUD
RATE: 115200
RS485 COM2 BAUD RATE:
19200
RS485 COM2 PARITY:
Even
RS485 COM2 RESPONSE
MIN TIME: 0 ms
, and
— The N60 is equipped with two independent serial communication
PARITY
— This setting specifies the minimum time before the rear RS485 port transmits after
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
See page 5-36
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
See page 5-37
See page 5-37
See page 5-40
Access in EnerVista
See page 5-41
See page 5-73
See page 5-73
See page 5-74
See page 5-75
Range: 19200, 115200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200 bit/s
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10