SYSTEM SETUP
5
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(
PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL
accordingly.
5.5.3.4 Example for use of sources
An example of the use of sources is shown in the following figure. A relay can have the following hardware configuration:
Increasing slot position letter -->
CT/VT module 1
8 CTs
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
5-116
Figure 5-47: Disturbance detector logic
ACTUAL
SOURCE 1
CURRENT PHASOR
_1
_2
_0
ACTUAL
SOURCE 2
CURRENT PHASOR
_1
_2
_0
ACTUAL
SOURCE 6
CURRENT PHASOR
_1
_2
_0
CT/VT module 2
4 CTs, 4 VTs
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
SETTING
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
_1 -
_1' >2*CUT-OFF
_2 -
_2' >2*CUT-OFF
OR
_0 -
_0' >2*CUT-OFF
Where ' is 2 cycles old
SETTING
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
_1 -
_1' >2*CUT-OFF
_2 -
_2' >2*CUT-OFF
OR
_0 -
_0' >2*CUT-OFF
Where ' is 2 cycles old
SETTING
PRODUCT SETUP/DISPLAY
PROPERTIES/CURRENT
CUT-OFF LEVEL
_1 -
_1' >2*CUT-OFF
_2 -
_2' >2*CUT-OFF
OR
_0 -
_0' >2*CUT-OFF
Where ' is 2 cycles old
) controls the sensitivity of the disturbance detector
CT/VT module 3
4 CTs, 4 VTs
CHAPTER 5: SETTINGS
FLEXLOGIC OPERAND
SRC 1 50DD OP
FLEXLOGIC OPERAND
SRC 2 50DD OP
FLEXLOGIC OPERAND
SRC 6 50DD OP
827092A3.CDR