Advertisement

PRODUCT SETUP
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-10: Commands mapping table
Description
Off
Virtual Input 1
Virtual Input 2
...
Virtual Input 64

5.3.5 Modbus user map

SETTINGS  PRODUCT SETUP  MODBUS USER MAP
 MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the address
in the
line (converted from hex to decimal format). The corresponding value displays in the
ADDRESS
"0" in subsequent register
5
An address value of "0" in the initial register means "none" and values of "0" display for all registers. Different
values can be entered as required in any of the register positions.
The UR Series Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser; enter
the IP address of the N60 in the web browser and click the option.

5.3.6 Real-time clock

5.3.6.1 Menu
SETTINGS  PRODUCT SETUP  REAL TIME CLOCK
 REAL TIME
 CLOCK
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchronizing
time delivered to the relay.
5-80
Value
0
1
2
...
64
ADDRESS 1:
VALUE:
0
ADDRESS 256:
VALUE:
0
lines automatically returns values for the previous
ADDRESS
SYNCRONIZING SOURCE:
None
REAL TIME CLOCK
EVENTS: Disabled
IRIG-B SIGNAL TYPE:
None
 PRECISION TIME
 PROTOCOL (1588)
 SNTP PROTOCOL
 LOCAL TIME
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
Range: Enabled, Disabled
Range: None, DC Shift, Amplitude Modulated
See below
See below
See below
CHAPTER 5: SETTINGS
line. A value of
VALUE
lines incremented by "1."
ADDRESS
ADDRESS