STATUS
6.2.9 RxGOOSE statistics
ACTUAL VALUES STATUS RxGOOSE STATISTICS RxGOOSE 1(16)
RxGOOSE 1
The N60 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
6.2.10 Digital counters
ACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8)
DIGITAL COUNTERS
Counter 1
6
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The
6.2.11 Selector switches
ACTUAL VALUES STATUS SELECTOR SWITCHES
SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6-6
RxGOOSE 1
stNum:
0
RxGOOSE 1
sqNum:
0
Counter 1
ACCUM:
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
0
value refers to the microsecond portion of the time stamp.
COUNTER 1 MICROS
SELECTOR SWITCH 1
POSITION: 0/7
SELECTOR SWITCH 2
POSITION: 0/7
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
Range: Current Position / 7
Range: Current Position / 7