Figure 5-76: Non-volatile latch operation table (N = 1 to 16) and logic
Latch n
Latch n
Latch n
type
set
reset
Reset
ON
OFF
Dominant
OFF
OFF
ON
ON
OFF
ON
Set
ON
OFF
Dominant
ON
ON
OFF
OFF
OFF
ON
5.6.9 FlexMath
SETTINGS FLEXLOGIC FLEXMATH SUMMATOR SUMMATOR 1(6)
SUMMATOR 1
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Latch n
Latch n
on
off
ON
OFF
Previous
Previous
State
State
OFF
ON
OFF
ON
ON
OFF
ON
OFF
Previous
Previous
State
State
OFF
ON
SUMMATOR 1 FUNCTION:
Disabled
SUMMATOR 1 INPUT
MODE: Signed
SUMMATOR 1 HOLD:
Off
SUMMATOR 1 PICKUP:
1000.000
SUMMATOR 1
HYSTERESIS: 3.0%
SUMMATOR 1 UNITS:
SUMMATOR 1 PU BASE:
1
SUMMATOR 1 INPUT1:
Off
SUMMATOR 1 INPUT2:
Off
SUMMATOR 1 INPUT6:
Off
SUMMATOR 1 SCALE1:
1.000000
SUMMATOR 1 SCALE2:
1.000000
SUMMATOR 1 SCALE6:
1.000000
SUMMATOR 1 POS1:
Off
Range: Disabled, Enabled
Range: Signed, Absolute
Range: FlexLogic operand
Range: –2000000.000 to 2000000.000 in steps of
0.001
Range: 0.1 to 50.0% in steps of 0.1
Range: 4 alphanumeric characters
Range: 1 to 2000000 in steps of 1
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: FlexLogic operand
FLEXLOGIC
5
5-167