Flexmath - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Figure 5-76: Non-volatile latch operation table (N = 1 to 16) and logic
Latch n
Latch n
Latch n
type
set
reset
Reset
ON
OFF
Dominant
OFF
OFF
ON
ON
OFF
ON
Set
ON
OFF
Dominant
ON
ON
OFF
OFF
OFF
ON

5.6.9 FlexMath

SETTINGS  FLEXLOGIC  FLEXMATH  SUMMATOR  SUMMATOR 1(6)
 SUMMATOR 1
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Latch n
Latch n
on
off
ON
OFF
Previous
Previous
State
State
OFF
ON
OFF
ON
ON
OFF
ON
OFF
Previous
Previous
State
State
OFF
ON
SUMMATOR 1 FUNCTION:
Disabled
SUMMATOR 1 INPUT
MODE: Signed
SUMMATOR 1 HOLD:
Off
SUMMATOR 1 PICKUP:
1000.000
SUMMATOR 1
HYSTERESIS: 3.0%
SUMMATOR 1 UNITS:
SUMMATOR 1 PU BASE:
1
SUMMATOR 1 INPUT1:
Off
SUMMATOR 1 INPUT2:
Off
SUMMATOR 1 INPUT6:
Off
SUMMATOR 1 SCALE1:
1.000000
SUMMATOR 1 SCALE2:
1.000000
SUMMATOR 1 SCALE6:
1.000000
SUMMATOR 1 POS1:
Off
Range: Disabled, Enabled
Range: Signed, Absolute
Range: FlexLogic operand
Range: –2000000.000 to 2000000.000 in steps of
0.001
Range: 0.1 to 50.0% in steps of 0.1
Range: 4 alphanumeric characters
Range: 1 to 2000000 in steps of 1
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: –2000.000000 to 2000.000000 in steps of
0.000001
Range: FlexLogic operand
FLEXLOGIC
5
5-167

Advertisement

Table of Contents
loading

Table of Contents