Advertisement

CHAPTER 5: SETTINGS
Figure 5-80: Power swing detect quadrilateral operating characteristics
The FlexLogic output operands for the power swing detect element are as follows:
POWER SWING
OUTER,
POWER SWING
are auxiliary operands that facilitate testing and special applications
POWER SWING TMR4 PKP
blocks selected protection elements, such as distance functions
POWER SWING BLOCK
blocks those protection elements that are intended to be blocked under power swings, but
POWER SWING UN/BLOCK
subsequently unblocked when a fault occurs after the power swing blocking condition has been established
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 5-79: Effects of blinders on the mho characteristics
X
MIDDLE,
POWER SWING
FWD RCA
INNER,
POWER SWING TMR2
PKP,
GROUPED ELEMENTS
R
PKP, and
POWER SWING TMR3
5-173