Direct Integer Inputs And Outputs - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

INPUTS/OUTPUTS
The
DIR ANA 1 INTEGRITY
FlexLogic operands are provided to indicate the most recent trigger condition: Only one operand can be active
32 FORCED
(logic 1) at any time. If a direct device is offline, all of the associated trigger operands are inactive (logic 0).
The figure illustrates the operation of the direct analogs feature. In this example, UR-1 is configured to use four out of its 32
analog channels. These four values are selected from two sources. UR-2 is configured to receive two out of the four analog
values sent, and UR-3 is set to receive three values. Note that
3.
5

5.9.8 Direct integer inputs and outputs

5.9.8.1 Menu
SETTINGS  INPUTS/OUTPUTS  DIRECT INTEGERS
 DIRECT INTEGERS
The direct integers feature allows the transmission of integer values between any two UR-series relays that support the
feature. The communication channel is the same as that used for the direct inputs and outputs. When the direct inputs and
outputs, direct analogs, and direct integers features are used together on the same channel, all UR-series relays must be
using firmware version 5.70 or higher.
5-238
to
DIR ANA 32
INTEGRITY,
DIR ANA 1 DEADBAND
Figure 5-121: Direct analogs sample application
UR-1
SRC1 P
SRC1 PF
Pool of
FlexAnalog
SRC2 FREQ
parameters
SRC1 V1 Mag
UR-2
Remote Analog 7
Pool of
FlexAnalog
parameters
Remote Analog 3
UR-3
Remote Analog 2
Pool of
FlexAnalog
Remote Analog 3
parameters
Remote Analog 9
 DIRECT INTEGER
 OUTPUTS
 DIRECT INTEGER
 INPUTS
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
to
DEADBAND, and
DIR ANA 32
is effectively being received at both UR-2 and UR-
SRC 2 FREQ
UR-1 is configured to send four
Analog Out 1
analog values as outputs 1, 2, 3,
and 4, respectively.
Analog Out 2
Analog Out 3
Analog Out 4
TX
RX
UR-2 is configured to receive
Analog In 7
and
SRC1 P
UR-1 as direct analog inputs 7
and 3, respectively.
Analog In 3
TX
RX
UR-3 is configured to receive
SRC1 PF SRC2 FREQ
Analog In 2
SRC1 V1 Mag
direct analog inputs 2, 3, and 9,
Analog In 3
respectively
Analog In 9
See below
See page 5-239
CHAPTER 5: SETTINGS
to
DIR ANA 1 FORCED
DIR ANA
from
SRC2 FREQ
,
, and
from UR-1 as
847007A1.CDR