CHAPTER 4: INTERFACES
Figure 4-5: Applying templates using the View in Template Mode settings command
Typical settings tree view without template applied.
Use the following procedure to display settings available for editing and settings locked by the template.
1.
Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2.
Apply the template by selecting the Template Mode > View All Settings option.
3.
Enter the template password then click OK to apply the template.
Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are
shown. The effect of applying the template to the phase time overcurrent settings is shown as follows.
Figure 4-6: Applying templates using the View All Settings command
Phase time overcurrent settings window without template applied.
4.1.6.5 Remove the settings template
It can be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and
it is necessary to define a new settings template.
1.
Select an installed device or settings file on the left side of the EnerVista UR Setup window.
2.
Right-click and select the Template Mode > Remove Settings Template option.
3.
Enter the template password and click OK to continue.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
ENERVISTA SOFTWARE INTERFACE
Typical settings tree view with template applied via
the
Template Mode > View In Template Mode
command.
Phase time overcurrent window with template applied via
the
Template Mode > View All Settings
The template specifies that only the
Pickup
settings be available.
842860A1.CDR
command.
and
Curve
842859A1.CDR
4-7
4