TESTING
Table 5-44: Test mode operation
TEST MODE
FUNCTION
Disabled
Isolated
Forcible
On restart, the
their default states.
5.11.3 Phasor Measurement Unit test values
SETTINGS TESTING PMU TEST VALUES PMU 1(6) TEST VALUES
PMU 1
TEST VALUES
5
5-318
In-service
Test mode
Critical fail
LED
LED
relay
Unaffected
Off
Normal
Off
On
De-energized No effect
Off
Flashing
De-energized Off
setting and the force contact input and force contact output settings revert to
TEST MODE FORCING
PMU 1 TEST
FUNCTION: Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
PMU 1 VA TEST
ANGLE: 0.00°
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
PMU 1 VB TEST
ANGLE: –120.00°
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
PMU 1 VC TEST
ANGLE: 120.00°
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
PMU 1 VX TEST
ANGLE: 0.00°
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
PMU 1 IA TEST
ANGLE: –10.00°
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
PMU 1 IB TEST
ANGLE: –130.00°
PMU 1 IC TEST
MAGNITUDE: 1.000 kA
PMU 1 IC TEST
ANGLE: 110.00°
PMU 1 IG TEST
MAGNITUDE: 0.000 kA
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
TEST MODE
Contact input and output behavior
FORCING
No effect
Normal
Contact outputs disabled
Normal
On
Controlled by forcing features
Range: Enabled, Disabled
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001