Direct Analog Inputs And Outputs - GE N60 Instruction Manual

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

INPUTS/OUTPUTS
UR IED 1
DIRECT OUT 2 = HYB POTT TX1
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (
setting).

5.9.7 Direct analog inputs and outputs

5
5.9.7.1 Menu
SETTINGS  INPUTS/OUTPUTS  DIRECT ANALOGS
 DIRECT ANALOGS
The direct analogs feature allows the transmission of analog values between any two UR-series relays that support the
feature. The communication channel is the same as that used for the direct inputs and outputs. When the direct inputs and
outputs and direct analog features are used together on the same channel, all UR-series relays must be using firmware
version 5.20 or higher.
Values are transmitted as unscaled floating point numbers. The units for these values are the base units of the FlexAnalog
value (for example, volts, amperes, watts, vars, VA, and so on).
Transmission of values occurs once every 250 ms, defined as the integrity period. Deadband and FlexLogic trigger checks
are performed once per power system cycle. Once a deadband or FlexLogic trigger occurs, the next transmission does not
occur until the next 250 ms integrity time-out.
5.9.7.2 Direct analog outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT ANALOGS  DIRECT ANALOG OUTPUTS  DIRECT ANALOG 1(32) OUTPUT
 DIRECT ANALOG 1
 OUTPUT
The direct analog outputs share the direct input and output settings for device ID, data rate, ring configuration, and
channel crossover.
5-236
Figure 5-120: Signal flow for direct input and output
DIRECT INPUT 5
DIRECT INPUT 6
 DIRECT ANALOG
 OUTPUTS
 DIRECT ANALOG
 INPUTS
ANALOG 1 VALUE:
Off
ANALOG 1 DEADBAND:
0.000
ANALOG 1 TRIGGER:
Off
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
See below
See page 5-237
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
Range: 0.000 to 1000000000.000 in steps of 0.001
Range: FlexLogic operand
CHAPTER 5: SETTINGS
842717A1.CDR
HYB POTT RX1