GE N60 Instruction Manual page 132

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP
When the "Server" Authentication Type is selected, the N60 uses the RADIUS server and not its local authentication
database to authenticate the user.
When the "Device" button is selected, the N60 uses its local authentication database and not the RADIUS server to
authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer), as login
accounts and the associated passwords are stored on the N60 device. In this case, access is not user-attributable. In cases
where user-attributable access is required, especially for auditable processes for compliance reasons, use server
authentication (RADIUS) only.
No password or security information is displayed in plain text by the EnerVista software or the UR device, nor are they ever
transmitted without cryptographic protection.
Only (TCP/UDP) ports and services that are needed for device configuration and for customer enabled features
5
are open. All the other ports are closed. For example, Modbus is on by default, so its TCP port 502, is open. But if
NOTE
Modbus is disabled, port 502 is closed. This function has been tested and no unused ports have been found
open.
CyberSentry settings through EnerVista
CyberSentry security settings are configured under Device > Settings > Product Setup > Security.
5-16
Figure 5-2: Login screen for CyberSentry
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents