GE N60 Instruction Manual page 268

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

FLEXLOGIC
Operand type
ELEMENT:
Selector switch
ELEMENT:
Setting group
ELEMENT:
Sub-harmonic stator
ground fault detector
5
ELEMENT:
Disturbance detector
ELEMENT:
VTFF (Voltage
transformer fuse
failure)
ELEMENT:
Summator
5-152
Operand syntax
SELECTOR 1 POS Y
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
SH STAT GND STG1 PKP
SH STAT GND STG1 DPO
SH STAT GND STG1 OP
SH STAT GND STG2 PKP
SH STAT GND STG2 DPO
SH STAT GND STG2 OP
SH STAT GND OC PKP
SH STAT GND OC DPO
SH STAT GND OC OP
SH STAT GND TRB PKP
SH STAT GND TRB DPO
SH STAT GND TRB OP
SRC1 50DD OP
SRC2 50DD OP
SRC3 50DD OP
SRC4 50DD OP
SRC5 50DD OP
SRC6 50DD OP
SRC1 VT FF OP
SRC1 VT FF DPO
SRC1 VT FF VOL LOSS
SRC1 VT NEU WIRE OPEN
SRC2 VT FF to SRC6 VT FF
SUMMATOR 1 OP
SUMMATOR 2 OP
SUMMATOR 6 OP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Operand description
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
Stage 1 of the sub-harmonic stator ground protection has picked up
Stage 1 of the sub-harmonic stator ground protection has dropped out
Stage 1 of the sub-harmonic stator ground protection has operated
Stage 2 of the sub-harmonic stator ground protection has picked up
Stage 2 of the sub-harmonic stator ground protection has dropped out
Stage 2 of the sub-harmonic stator ground protection has operated
Ground over current element of the sub-harmonic stator ground protection
has picked up
Ground over current element of the sub-harmonic stator ground protection
has dropped out
Ground over current element of the sub-harmonic stator ground protection
has operated
Sub-harmonic stator ground module trouble has picked up
Sub-harmonic stator ground module trouble has dropped out
Sub-harmonic stator ground module trouble has operated
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 5 disturbance detector has operated
Source 6 disturbance detector has operated
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 10% and V1 below 5% of nominal)
Source 1 VT neutral wire open detected. When the VT is connected in Delta,
do not enable this function because there is no neutral wire for Delta
connected VT.
Same set of operands as shown for SRC1 VT FF
The summator 1 result is greater than the summator 1 pickup
The summator 2 result is greater than the summator 2 pickup
The summator 6 result is greater than the summator 6 pickup
CHAPTER 5: SETTINGS