GE N60 Instruction Manual page 157

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS  PRODUCT SETUP  SECURITY  COMMUNICATIONS  DNP / IEC104 POINT LISTS  BINARY INPUT /
MSP POINTS
 BINARY INPUT / MSP
 POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the N60 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS  PRODUCT SETUP  SECURITY  COMMUNICATIONS  DNP / IEC104 POINT LISTS  ANALOG INPUT
/ MME POINTS
 ANALOG INPUT / MME
 POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the N60 is restarted.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are
NOTE
ignored.
5.3.4.12 IEC 61850 protocol
The N60 is provided with optional IEC 61850 communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section in chapter 2 for details.
The IEC 61850 settings are accessible in EnerVista software or a substation configuration language (SCL) generating tool.
The path is Settings > Product Setup > Communications > IEC 61850. The settings are not accessible from the front panel
of the device.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
 ANALOG INPUT / MME
 POINTS
Point: 0
Off
Point: 1
Off
Point: 255
Off
Point: 0
Off
Point: 1
Off
Point: 255
Off
See below
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
PRODUCT SETUP
5
5-41

Advertisement

Table of Contents
loading

Table of Contents