GE N60 Instruction Manual page 260

Network stability and synchrophasor measurement system
Hide thumbs Also See for N60:
Table of Contents

Advertisement

SYSTEM SETUP
PMU AGGREGATOR 1: NUMBER OF ASDUs
through to 4.
Table 5-18: Number of ASDUs
Settings for
Transmission
ASDU
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
5.5.6.20 Control blocks
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  IEC 90 – 5 MSVCB01 (02-04) CONFIGURATION
 IEC 90-5 MSVCB
 CONFIGURATION
5
— The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
MSVCB 1 SVENA
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where "1"= Enabled and "0"=Disabled. The figure shows the logic for setting the SvEna control bit.
5-144
— This setting sets the number of Application Service Data Units (ASDUs) from 1
MSVCB 1 SVENA:
OFF
MSVCB 1 CLIENT CTRL:
OFF
MSVCB 1 SVENA DEFLT:
OFF
MSVCB 1 CONFREV:
1
MSVCB 1 PRIORITY:
4
MSVCB 1 IP CLASS:
46
MSVCB 1 VID:
0
MSVCB 1 APPID:
0
MSVCB 1 DEST. IP:
224.0.0.0
MSVCB 1 SECURITY:
0
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
Range: 0 to 7
Range: 0 to 252
Range: 0 to 4095
Range: 0 to 16383
Range: 0 to 255.255.255.255
Range: 0 to 2

Advertisement

Table of Contents
loading

Table of Contents