IMPORTANT
• Ensure the exact same electronics assembly model is being replaced. Verify the assembly part numbers are identical before
beginning installation. Refer to
• For valve the mechanical and electrical installation, follow the SV2 Series Valve Replacement Electronics installation
instruction document, 32-00039, which is packed with the replacement assembly.
• For step-by-step programming setup instructions, consult the HMI / PC Tool user manual, 32-00031.
• Ensure that the SOLENOID 1 and SOLENOID 2 internal wiring is properly re-connected per the original arrangement.
Failure to do so may cause unnecessary fault conditions.
• The maximum tightening torque to fasten the electronics assembly to the electrical enclosure is 1.26-1.54 Nm
(11-13.63 in-lbf).
When replacing the electronics assembly in the field, retainment of the most of the Pressure Module and Fuel Air Ratio Module
programmed settings should occur, unless those accessories are replaced at the same time as the main valve electronics
assembly. It is recommended, however, to perform/verify the valve programming as was done during the original installation.
The HMI / PC Tools have embedded guided setup wizards for easy commissioning. Detailed step-by-step programming
instructions are provided in the HMI / PC Tool user manual, 32-00031.
Replacement Solenoids
Specifications
Models:
Valve size AB: 1 inch (DN25)
Voltages: 24, 100-120, 200-240VAC
Valve size CD: 1 ½ and 2 in (DN40 and DN50)
Voltages: 100-120, 200-240VAC
Documentation:
32-00038, Replacement Solenoid Installation Instructions
Introduction and Replacement Solenoid Selection
The SV2 Series individual solenoids can be replaced in the field without replacing the entire valve, should the need arise.
Replacement solenoid part numbers are identified by 'COIL', followed by the valve body size identifier and applicable voltage.
Each replacement solenoid will work on all valve intelligence levels and models as indicated in
As the various valve sizes and voltages are released, the associated replacement solenoid kits will also be released.
Replacement solenoids are sold and shipped one (1) per box.
SV2 Series Safety Shut-off Valves
V2F, V2V
Table 14
and/or the model information on the electronics assembly installed on the valve.
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL