SV2 Series Safety Shut-off Valves
Fig. 57: Correction Curve setup.
Adding Points to Create the Correction Curve (Addition button)
The Correction Curve needs to be built starting with the Minimum point. To set the Minimum load point, run the
appliance at minimum load and set the gain factor for this load by selecting Start Point Commissioning and changing
the gain factor with the arrow keys until the excess air level has stabilized at the right level. Select the Set Min button to
store the gain factor for this point.
Increase the appliance load and repeat this process for maximum and intermediate loads. The Set Max button records
the maximum load point while the Add Generic button records any intermediate load points.
While defining the gain setting for various loads, additional commissioning data can be entered. To enable this function
select Enter Optional Data.
The commissioning of any point can be interrupted by selecting the Stop Point Commissioning button.
102