Honeywell SV2 Series User Manual page 58

Safety shut-off valves
Table of Contents

Advertisement

SV2 Series Safety Shut-off Valves
Mounting
The Pressure Module can be mounted in any of the four (4) positions on the valve body and is keyed for specific mounting
orientation. The seals of the Pressure Module are designed to cover the center and upper pressure access ports of each
mounting location.
Cord length of each Pressure Module is long enough to fit all applicable valve sizes when mounted on the same side as the valve
electronics enclosure. On smaller valve sizes, the extra cord length may be placed inside the electronics enclosure or dressed to
one of the provided wire clips on the NEMA 1 / IP20 valve electrical enclosure.
Available pressure port locations for V1 and V2 valve seats on both sides of the valve are shown in
Module placement and associated functionality can be found in
are valve model and intelligence level dependent.
NOTES:
• Accessing the Inlet (I) port of mounting locations A and C on V1 for Pressure Module use is not allowed.
• For detailed installation instructions, refer to the Pressure Modules Installation Instructions, document 32-00017.
• If you need to replace a pressure access location cover, the tightening torque should be between 1.36 to 1.81 Nm (12 to
16 in-lbf).
• If you need to replace a pressure access port plug, the tightening torque should be 6 to 8 Nm (53 to 71 in-lbf).
2-27/64
(61)
Fig. 25: Pressure Module.
2-7/8
(73)
2-57/64
(73)
M35484
Table
12. Note that available mounting locations and functions
58
Fig. 16 and Fig.
18. Pressure
32-00029—02