Table Of Contents - Honeywell SV2 Series User Manual

Safety shut-off valves
Table of Contents

Advertisement

Fault
Fault
Category
Description
Lo-Gas pressure
lockout
Hi-Gas pressure
lockout
Lo-/Hi-Gas
Pressure
pressure not
Limits
configured
Pressure out of
range
SV2 Series Safety Shut-off Valves
V2F, V2V
Detailed Description
Low gas pressure below
threshold
High gas pressure above
threshold
configured for low and high
gas pressure functions
Pressure out of the allowed
Pressure Module range.
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Remediation Steps
3.) Recommission Low gas pressure
setting as necessary.
1.) Reset valve and burner management
system, observing burner operation for
proper pressures.
necessary.
3.) Recommission High gas pressure
setting as necessary.
NOTE: Low and High gas pressure
settings must be configured before valve
will be operational
1.) Commission Low and High gas
2.) If the pressure module is correct, reset
valve and burner management system,
observing burner operation for proper
pressures.
3.) Adjust appliance regulator as
necessary.
4.) If inlet pressure is higher than Pressure
Module rating, remove power and shut off
gas supply and replace Pressure Module
with higher rated model.