Honeywell SV2 Series User Manual page 185

Safety shut-off valves
Table of Contents

Advertisement

Fault
Fault
Category
Description
Fuel/Air
FARMOD light-
off S2b/S1 ratio
SV2 Series Safety Shut-off Valves
V2F, V2V
Detailed Description
The Fuel/Air Ratio Module
S2b/S1 ratio was outside the
commissioned window.
This can potentially be
caused by a change in
ignition load or ignition fan
speed.
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Remediation Steps
When combined with fault 42 and/or 44
it's an indication the fan speed is wrong or
there are flue system issues.
1.) Check that air duct is clear free of any
foreign bodies and pollution.
2.) Check that blower is running at a
proper rate.
3.) Check Fuel/Air Module signal
connections for proper engagement.
4.) Reset valve and burner management
system.
5.) If fault persists, recommission light off
sequence. Record new pre-ignition air
proving values by checking the Record
Ign. Air Level box on the Ignition Setup
page once system is stabilized.
6.) Check combustion by measuring O2
and CO2 levels.
7.) If fault persists, replace Fuel/Air Ratio
Module.
8.) Accept new Fuel/Air Ratio Module on
the FARMOD tab in the Setup & Tests
menu of user interface.
9.).Recommission partially or fully as
desired.
If fault appears independently, the likely
cause is a corrupt S2b sensor inside the
FARMOD.
1.) Reset valve and burner management
system.
2.) If fault persists, replace Fuel/Air
Module.
3.) Accept new Fuel/Air Ratio Module on
the FARMOD tab in the Setup & Tests
menu of user interface.
4.).Recommission partially or fully as
desired.
185
Comments Fault
#
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

V2fV2v

Table of Contents