Honeywell SV2 Series User Manual page 215

Safety shut-off valves
Table of Contents

Advertisement

Address
Type
Valve
Model
Dec
Hex
64
40
65
41
66
42
Fuel / Air
V2V
67
43
218
DA
219
DB
SV2 Series Safety Shut-off Valves
V2F, V2V
Intelligence
Description
Level
Ignition Setpoint
Ignition Period
Ignition Ramp Offset
Standard
Ignition Default Position 2
S1 pre-ignition lower threshold
S1 pre-ignition upper threshold
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
Data
Content
Type
% of RUN mode target amplification as
given by Fuel/Air curve at the ignition load
S16
(ignition S1). Determines the target value
for fuel/air control during the Ignition Period
(holding register 65)
Ignition period in seconds. Includes the
Ramp Period, the Hold On Period and the
remaining period in which the controlled
U16
amplification setting can be changed
relative to the normal amplification setting
at the start load / RUN as governed by the
Ignition Setpoint (holding register 64)
This sets the number of steps that the
Learnt Pos. 2 is reduced or offset during
ignition. Once the valve seats are powered,
the stepper motor moves from this position
S16
to the Learnt Pos. 2 position during the
Ignition Ramp Period time (HR341)
Register content is scaled by 4
(i.e. value of 4 is one full step)
In half steps.
Used for the first/initial stepper motor
ignition start position 2 by OEM in lab.
U16
Note that valve will learn and record the
appropriate stepper motor position with
each light-off. Saved as the Learnt Pos. 2
(IR125)
A % that the air S1 signal can be below the
recorded / commissioned air signal during
U16
ignition. If the air signal drops below this
value the valve will lockout
A % that the air S1 signal can be over the
recorded / commissioned air signal during
U16
ignition. If the air signal raises above this
value, the valve will lockout.
215
Range
Default
Value
Min
Max
70
150
100
Ignition
Ramp time
(HR341)
+ Ignition
5 * 10
3 * 10
Hold
On time
(HR340) +
1 sec
-4 * 50
-4 * 34
-32768
1.0in /
DN25
=821
1.5in /
0
DN40
-32768
=1412
2.0in /
DN50
=1412
50
95
80
105
150
120

Advertisement

Table of Contents
loading

This manual is also suitable for:

V2fV2v

Table of Contents