Honeywell SV2 Series User Manual page 218

Safety shut-off valves
Table of Contents

Advertisement

SV2 Series Safety Shut-off Valves
Table 35. Input Register Mapping
Address
Type
Dec
Hex
2
2
3
3
5
5
6
6
70
46
71
47
72
48
73
49
74
4A
75
4B
76
4C
77
4D
78
4E
95
5F
96
60
General
214
D6
215
D7
216
D8
217
D9
225
E1
226
E2
227
E3
228
E4
229
E5
230
E6
231
E7
232
E8
233
E9
234
EA
235
EB
236
EC
237
ED
238
EE
239
EF
240
F0
241
F1
242
F2
Valve
Intelligence
Description
Model
Levels
Valve electronic software revision
Intelligence level identification
# of currently active alarms with highest priority
Valve status information
Fault code number 0
Fault code number 1
Fault code number 2
Fault code number 3
Fault code number 4
Fault code number 5
Fault code number 6
Fault code number 7
Valve system states
Valve VAC signal status
All
Standard
Valve accumulated operation time in hours
Valve accumulated number of cycles. Either
MV1 or MV2, whichever is higher.
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Valve factory data
Data
Content
Type
High byte major
U8 + U8
Low byte minor
U16
Standard=0
S16
-32768=No alarm active alarm
0=Reset button
1=MV1 open
2=MV2 open
Bit array
4=Pressure Module communication OK
6=Safety parameter verification required
7=Lockout
8=Valve cycle counter limit reached
Fault code number corresponding to the fault code/time
Bit array
stamp/cycle count in input registers 139-213
Enum
Refer to
Low status word.
Bit array
Refer to
High status word.
Bit array
Refer to
U16
Upper 2 bytes
Lower 2 bytes
U16
Resolution 0.25 hr
U16
Upper 2 bytes
U16
Lower 2 bytes
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
Main electronics factory data string of characters ended by
62 x Char
either ASCII-0 or end of register array.
62 x Char
Two characters per register
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
62 x Char
218
Table
31.
Table
36.
Table
36.
32-00029—02