Honeywell SV2 Series User Manual page 211

Safety shut-off valves
Table of Contents

Advertisement

Table 29. Query Message Format for SV2 Series Valve Status / Function Code 17.
Node Address
Function Code
Varies (1 byte)
Table 30. Response Message Format for SV2 Series Valve Status / Function Code 17.
Node
Function
Address
Code
Varies
17 (1 byte)
(1 byte)
Table 31. System States.
State Number
Alias
0
NormalOperation
1
SoftLockout
2
HardLockout
3
Lockout
6
GasON
7
GasOFF
13
StartUp
14
Reset
15
Run
16
InterlockStringTest
17
SafetyRelayTest
The SV2 Series valve Modbus address space is organized in two segments; holding registers and input registers. Refer to
Table 32
for the read and write access function codes.
Table 32. Modbus Function Codes.
Segment
Holding registers
Input registers
The Holding Register limits and attributes are as follows:
• The minimal value that can be written into a Holding Register <address> can be read from the Holding Register <address +
10000>.
• The maximum value that can be written into a Holding Register <address> can be read from the Holding Register <address +
20000>.
The bit array register attributes of a Holding Register <address> can be read from the Holding Register <address+30000>. The
meaning of Holding Register bits 0-3 can be found in
SV2 Series Safety Shut-off Valves
V2F, V2V
CRC
17 (1 byte)
Low, High (2 bytes)
Number
SV2 Valve
Response
State
Bytes
Number
35
Refer to
Table
31.
(1 byte)
Description
SV2 valve is operable.
Soft-lockout. Recovery after 1 hour or upon a user reset.
Soft-lockout. Recovery upon a user reset.
Hard or Soft lockout(s) are active.
Gas is running – both SSOVs are opened.
Gas is stopped – at least one SSOV is closed.
Safety tests performed after power-up or after lockout is terminated.
User has pressed a push-button during normal operation. Gas valves are turned
OFF and faults are cleared.
Valve has gone through StartUp and is running.
An interlock string test performed after power-up or after lockout is cleared.
A safety relay test performed after power-up or after lockout is cleared.
Read Access Function Code
3
4
Table
SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
SV2 Valve Factory Data
String terminated by 0 or maximum size 62 characters
Write Access Function Code
6 or 16
----
33.
211
CRC
Low, High
(2 bytes)
Access
Read / Write
Read Only